Loading knowledgebase suggestions...
» Category: Elegance XL Installation
(Go back)
» Articles in this category:
 |
|
 |
|
 |
Each relay module (4 relays) in the panel is rated for 16A max.
The 16A is split up as follows:
You can have up to 8A on any one relay in the module, with the remaining 8A split up among the oth... |
|
 |
The Elegance HVRB is rated as follows per UL:
100A max per board at 277VAC
6.25A per relay using all 16 relays, up to 277VAC
15A per relay if only using up to 6 alternating relays, up to 277VAC |
|
 |
In the Elegance XL panel, the phases are determined by the relay modules.
Each pair of relay modules must be supplied with the same phase in order for dimming to occur smoothly.
Relay Modules 1 &a... |
|
 |
What are the maximum distance the components can be from the Elegance XL MCP?
The maximum distance the components can be from MCP are:
Relay driver board - 1,000 feet
High voltage relay board -... |
|
|
|
 |
|
 |
Powered by Help Desk Software HESK - brought to you by Help Desk Software SysAid |